SERAT heat recovery and delivery
The Heat-Service Module matches available source heat to a specific customer temperature and demand.
Normal operation / Fault response Interactive replay
Starting conditions
Source temperature and customer demand have been measured. A suitable delivery, storage or rejection path is available.
Operating sequence
Measure source and demand
Read the source temperature, available heat and required delivery conditions at the declared service boundary.
Choose the heat path
Use isolated direct exchange when the temperature difference supports it. Draw from storage or use a mapped heat pump when appropriate.
Store or deliver
Direct recovered heat can charge the reference store. Available heat is sent to the customer at the defined service temperature.
Meter the balance
Account for delivered heat, storage changes, compressor and auxiliary electricity, backup supply and losses.
Handle demand loss
If the customer stops taking heat, SERAT checks the available rejection path. The Earth Research Facility study uses four independently isolatable 4 MW dry cooler groups. At the assumed rating, one group out leaves 10.8 MW for dispatch after holding 10% in reserve.
Hold and recovery
If demand disappears, verify a qualified storage or heat-rejection path before accepting more source heat.
Model and references
Open the interactive cycleZENIT concept procedure. Models and replays use illustrative conditions.